Frost-proof valve series 108, without ambient air sensor
XXX.XX
€/unit
|
XXX.XX
€/unit
Description • To prevent frost damage to outdoor units of Monoblock heat pumps • Drains the heating water if there is a risk of frost due to a power failure, defective Circulation pumps or similar • Installation required outdoors in the supply and return flow pipe • Installation in vertical pipework • Opens at a medium temperature of +3°C, closes at a medium temperature of +4°C Technical data: • Ambient air temperature: -30°C to 60°C • Media: water, water/glycol mixture up to 30% • Housing material: brass • Discharge capacity: - 0.5 l/h (at -5°C and 3 bar) - 1 l/h (at -20°C and 3 bar) • For heating operation up to 65°C • Without ambient air sensor • Operating pressure: max. 10 bar • Operating temperature range: 0°C to 65°C See catalogue
|
Products |