Heating controller CETA 106
XXX.XX
€/unit
Description Not only simple standard systems can be controlled via CETA, more demanding applications can also be achieved by combining several CETA modules. Up to 4 control devices can be combined with one another due to this modular expansion. The individual controller communicate with each other via a databus. Every CETA controller can also be operated independently. Technical data: • Operating voltage: 230 V / 50 Hz • Max. power consumption: approx. 2.1 VA • Fuse: 6.3 A • Output relay contact load: 2(2) A • Ambient temperature: -10...+50°C • Protection type: IP 30 Protection class according to EN 60730: II • Housing dimensions (W x H x D): 145.5 x 161 x 48 mm • Housing material: ABS Vo • Mains connection technology: Screw terminals 1.5 mm² • Sensor connection technology: Screw terminals 0.5 mm² • Mounting: Wall or top-hat rail Mixed heating circuit: Weather-bad control of a mixed heating circuit via three relay outputs, switching time program with two switching cycles per day, room influence or room control via optional room station (CETA RC), different operating modes can be selected, summer switch-off, frost protection function, information displays for temperatures and switching states. Temperature differential controller (can be activated): with a relay output and two sensor inputs, ideally suited for controlling solar systems and solid fuel boilers Delivery contents: 1x Ceta 106, 1x VF 202 B contact sensor, 1x AF 200 contact sensor Optional accessories: CETA RC, CETA SMS, sensor for temperature differential control Technical data