Hydraulic module Easyflow Logic 1
XXX.XX
€/unit
Description Heating and hot water preparation design • For condensing boiler systems with a mixed or unmixed heating circuit • Optimal condensing technology utilisation as the radiator’s high return temperature is mixed into the underfloor heating or wall heating system’s flow, and thus the total return is cooled down to such a point where condensation always occurs in the condensing boiler • Simple fixing due to stable metal base plate • Lower investment and operating cost as a pump in the direct circuit is not required (a heating device pump is used) • Compact and fully pre-assembled • Fully pre-wired (in the design with control system) Direct circuit flow: 1 x red thermometer ball valve 0-120°C 1 x overflow valve Direct circuit return: 1 x blue thermometer ball valve 0-120°C with adjustable check valve Mixer circuit flow: 1 x red thermometer ball valve 0-120°C 1 x circulating pump Wilo Para 15/6 SC 1 x bivalent mixer Mixer circuit return: 1 x blue thermometer ball valve 0-120°C with adjustable check valve Technical data: • Max. operating temperature: 95 °C • Max. operating pressure: 6 bar • Connections: DN25(1“) IT • Check valve: 20 mbar • KVS value direct circuit: 5.0 • Kvs value mixer circuit: 4.0 • Max. output direct circuit: 35 kW (Δt 20 K) • Max. output mixer circuit: 12 kW (Δt 8 K) • Max. flow rate direct circuit: 1510 l/h (Δt 20K) • Max. flow rate mixer circuit: 1300 l/h (Δt 8K) • Heat generator centre dimension: 125 mm • Heating circuit centre dimension: 90 mm • Material: brass, copper • Insulation: EPP • Dimensions (with insulation) HxWxD: 516x400x180 mm • Weather-compensated • Fully pre-wired • Incl. control system, mixer motor, changeover valve and sensor See catalogue
|