Heating circuit set Easyflow DN20, thermal control circuit with constant value
XXX.XX
€/unit
|
XXX.XX
€/unit
Description Flow: 1 x flow pump flange ball valve with thermometer handwheel (thermometer ring, red, 0-120°C) • 2 x union nut and seal • 1 x screw connection DN 20 (3/4") • Incl. U-pump Wilo Para 15/6 SC, installation length 130 mm Return: 1xreturn pump flange ball valve with thermometer handwheel (thermometer ring blue, 0-120°C) and adjustable check valve by turning handwheel 45° • 1 x brass pipe • 1 x screw connection DN 20 (3/4") • Supply and return flow can be exchanged Heating circuit set technical data: • Max. operating temperature: 110 °C • Max. operating pressure: 10 bar • Boiler side connections: DN 20 (3/4”) ET • Consumer side connections: DN 20 (3/4”) IT • Check valve: 20 mbar • Centre dimension: 90 mm • Material: brass • Insulation: EPP • Dimensions (with insulation) HxWxD: 302 x 180 x 142 mm Technical data pump: • Nominal size: DN 15 (1/2") x DN 25 (1") • Installation length: 130 mm • Discharge head: 6.0 m • Operating voltage: 230 V/AC • EEI: ≤ 0.20 • Proportional characteristic pressure curve: 3 • Constant pressure characteristic curve: 3 • Constant speed: 3 • Material: KTL-coated grey cast iron • Can be set from 20 to 45°C • KVS value: 2.0 • Max. output: 4.5 kW • Max. flow rate: 500 l/h • Flow: 1x 3-way fixed value mixing valve • Return: T-piece for 3-way fixed value mixing valve See catalogue
|
Products |