Gas flow monitor

Short description
  • Model GST for domestic installation according to DVGW-VP305, as a measure to actively deter manipulation in accordance with TRGI
    Technical properties:
    Horizontal installation: for metal conductors and plastic pipes
    Vertical installation: only for metal conductors, flow direct from bottom upwards
    Operating pressure: 15-100 mbar
    Operating temperature: -20°C to +60°C
    Pressure loss: dp<0.5 mbar
    Overcurrent: VL <30 lt/h at 100 mbar
    External temperature resistance: 925 °C - 5 bar
    Internal temperature resistance: 200 °C
    Area of application: all gas types according to EN437 and DVGW G260/1
    Function:
    the flow monitor blocks the line when the flow rate selected is achieved. After the cause is rectified, pressure compensation occurs via an overflow opening, which enables the safety device to re-open.

    Construction:
    the internal springs do not come into contact with the flow of gas, which means they do not get dirty, ensuring a long service life. The overview opening is also protected in the open position to safeguard the re-opening function.